Electrical British Standard Chapter 51-53 general Overview

 CHAPTER 51

Chapter 51 focused on the selection and erection of electrical equipment. This chapter would have provided guidance and standards for the appropriate selection, installation, and arrangement of various electrical equipment and components used in electrical installations. It provides common rules for compliance with, measures of protection for safety requirements, for proper functioning for intended use of the installation Requirements appropriate to the external influence.

General Requirements

Compliance with Standards

Equipment Standards

All equipment must comply with the relevant British or Harmonized Standard applicable to its intended use. The edition used should be the current one with applicable amendments. If equipment complies with a foreign national standard based on an IEC Standard, the designer must verify that it offers safety levels equivalent to the British Standard.

Non-Standard Equipment

Equipment not covered by a British or Harmonized Standard, or used outside its standard scope, must provide the same degree of safety as compliance with the regulations.

Operational Conditions and External Influences

Operational Conditions

Voltage

Equipment must be suitable for the nominal voltage of the installation, accounting for the highest and lowest expected voltages. In IT systems, equipment must be insulated for the nominal voltage between lines.

Current

Equipment should handle the design current, including capacitive and inductive effects, and any abnormal currents for periods defined by the protective devices. Switchgear, protective devices, and accessories should not be connected to conductors operating above 70°C unless specified by the manufacturer.

Frequency

If frequency affects equipment characteristics, the equipment's rated frequency must match the nominal frequency of the circuit supply.

Power

Equipment should be selected based on power characteristics suitable for the demanded duty.

Compatibility

Equipment must not cause harmful effects to other equipment or impair the supply during normal service, including switching operations.

Impulse Withstand Voltage

Equipment must have an impulse withstand voltage at least equal to the minimum required at the installation point, as defined in Section 443.

External influences

Equipment shall be of a design appropriate to the situation in which it is to be used or its mode of Installation shall take account of the conditions likely to been countered.

Accessibility

Every item of equipment shall be arranged so as to facilitate its operation, inspection and maintenance and access to each connection.

Identification and notice

A label or other suitable means of identification Shall be provided to indicate the purpose of each item of switchgear and control gear. Here there is identification of conductors by colour or numbers and conduits.

Prevention of mutual detrimental influence.

Electrical equipment shall be selected and erected so as to avoid harmful influence between the electrical installation and any non- electrical installation envisaged.

Electromagnetic compatibility

The immunity levels of equipment shall be chosen taking into account the electromagnetic influences that can occur when connected and erected for normal use, BS NE  50082. Equipment shall be chosen with sufficiently low emission levels so that it cannot cause unacceptable electromagnetic interference with other electrical equipment by electrical conduction or propagation in air (BS 50081).

 CHAPTER 52

Chapter 52 outlines the regulations for selecting and erecting wiring systems, ensuring that they are appropriate for the intended purpose and safe under various conditions. Wiring systems must be selected and installed according to their environmental conditions, such as temperature, humidity, and the presence of chemicals. Considerations include the mechanical strength of the wiring system and its ability to withstand external influences.

External influences

The selection of wiring systems must take into account external factors like water, dust, mechanical damage, and temperature variations. Specific wiring types and installation methods are recommended based on the external conditions they will face.

Types of wiring systems

Various types of wiring systems include cables, bus bar trunking systems, and flexible cords. Each type has specific standards and regulations regarding their installation and use.

Accessibility

Wiring systems should be accessible for maintenance, inspection, and repair. Adequate space must be provided around wiring systems to allow for safe and effective maintenance activities.

Proximity to non-electrical Services

Electrical services should not interfere with nonelectrical services (e.g., water, gas, steam). Proper spacing or shielding should be used to prevent interactions that could cause harm or degrade performance.

Maintainability

Wiring systems must be designed and installed to facilitate maintenance without compromising safety. Provisions should be made for safe access to parts of the wiring system that may require maintenance.

 CHAPTER 53

Chapter 53 establishes general requirements for protection, isolation, switching, control, and monitoring. It covers the selection and erection of devices to ensure safety and proper functionality of electrical installations.

General requirements

Equipment Selection

All equipment must be selected and installed considering the intended use and external influences to ensure safety and functionality.

Multiphase Circuits

In multiphase circuits, the moving contacts of all poles in a multipole device must make and break simultaneously, except for the neutral contact, which may close before and open after the others.

Neutral Conductors

Single pole switching or protective devices should not be inserted solely in the neutral conductor in multiphase circuits.

Multifunction Devices

Devices with multiple functions must meet the requirements for each function specified in this chapter.

Fixing of equipment

Equipment must be fixed according to the manufacturer's instructions, ensuring connections are not subject to stress or strain. Unenclosed equipment must be mounted in a suitable box or enclosure and securely fixed to the building structure.

Devices for fault protection by automatic disconnection of supply

Overcurrent Protective Devices, these include fuses, circuit breakers, and other devices that protect against overcurrent conditions.

Residual Current Devices (RCDs) which are used to disconnect the supply in case of earth faults.

Insulation Monitoring Devices (IMDs), these are devices used to monitor insulation resistance in IT systems and alert users to potential faults.

Devices for protection against fire

 Devices must be installed to prevent electrical fires, considering the installation environment and the nature of the electrical loads.

Devices for protection against overcurrent

Overcurrent protective devices must be capable of breaking any overcurrent occurring in the circuit.

Overload Protection devices must be selected to protect wiring systems from excessive currents due to overloads.

Fault Current Protection devices must be capable of disconnecting fault currents within specified time limits.

Devices for protection against under voltage

Protective devices should also address under voltage conditions, preventing potential damage to equipment.

Coordination of protective devices

Protective devices must be coordinated to ensure proper operation without unnecessary interruptions. Devices must be selected to ensure that only the faulty section is disconnected, preserving the supply to the rest of the system. Also secondary protection should be provided in case the primary device fails.

Proper coordination between switching and protective devices is crucial for system safety and reliability.

Isolation and Switching

Isolating devices must safely disconnect electrical circuits for maintenance or emergencies. Specific switches must be used to isolate equipment for safe mechanical maintenance.

Emergency switches must be easily accessible and operable to disconnect power in hazardous situations.

Devices for functional switching must control electrical equipment as needed.

Special switches may be required to isolate power during firefighting operations.

Monitoring

Insulation Monitoring Devices (IMDs), these devices are used to monitor insulation resistance in IT systems to detect faults.

Residual Current Monitors (RCMs), these devices detect and monitor leakage currents, providing early warnings to prevent protective device operation due to leakage.


1 Comments

Post a Comment
Previous Post Next Post